EXsmart2 and MIFARE Mullion are compatible with all standard control panels.
Mounting
All the readers be fixed directly to the mounting surface but only the square readers will fit onto a standard electrical back-box (not supplied) to allow adequate clearance for the connection terminal block. Connect all wires to the relevant connections for the reader (see over page).
1 Drill and screw the reader directly to the wall or Knock-out access for the cable in the rear of the electrical back-box, fit the back-box into the wall, and run the cable through the back box
2 Drill and screw the reader directly to the wall or Knock-out access for the cable in the rear of the electrical back-box, fit the back-box into the wall, and run the cable through the back box
3 Place the cover over the reader and gentle apply pressure to push the cover back until it is locked in placed.
4 If the reader is to be mounted externally, apply a bead of non-caustic sealant between the top and side edges of the reader and the mounting surface
Removal of Front Cover
To remove the front cover once it has been fitted, Insert a flat blade such as a screwdriver into the slot as shown and lever the cover away from the base.
Connections
The MIFARE Mullion is supplied pre-wired whereas the EXsmart² has a terminal block plug allowing you to pre-wire the connection. It supports all standard access control standards including TDSi's MICROgarde, Excel, EXpert and EXpander control panels. Although any 6 core screened cable could be used TDSi recommend 7/0.2 screened e.g. Beldon 9730 (max. cable length 150m when used with MICROgarde I and MICROgarde II, EXcel, EXpert, EXpander Controllers).